Commercial building compliance checklist.

In short

A commercial building compliance checklist lists the inspections, tests and assessments the law expects whoever controls a building to have done, how often, and the record that proves each one. Most come from the Fire Safety Order, the workplace and work equipment maintenance duties, LOLER, the pressure systems rules, COSHH, the gas, asbestos and electricity rules, the F-gas rules and the energy performance regulations. Only a few intervals are fixed by law; the rest come from British Standards and your own risk assessments. The 31 checks below are the ones a facilities register should start from, and a building keeps only those that apply.

What is a commercial building compliance checklist?

A commercial building compliance checklist is the list of statutory checks for an office, shop, industrial unit or mixed-use building: the fire risk assessment and the fire safety systems, electrical and gas safety, water hygiene, asbestos, lifts, pressure systems, ventilation, refrigeration, air conditioning and energy performance. For each check it says what the law or the standard asks, how often it is done, and what record proves it. It becomes a register once each line carries the date it was last done, the next due date and the certificate behind it.

Who is responsible for these checks?

It depends on the duty. Under the Fire Safety Order the responsible person, usually the employer or whoever controls the premises, must have a suitable and sufficient fire risk assessment and keep fire safety equipment under a suitable system of maintenance; where premises are part of a larger building, article 17 lets them make arrangements with the other occupiers, who must cooperate. The duty to manage asbestos falls on whoever has a contractual or tenancy obligation to maintain or repair the premises, or control of them where there is no such contract, shared in proportion. Employers must maintain the workplace, its equipment and work equipment in efficient working order. In a multi-let building the lease decides who does what, which is why a landlord, a managing agent and an FM provider often hold different parts of the same list.

Which intervals does the law set, and which come from standards?

The law fixes only a few. Lifts and lifting equipment that carry people must be thoroughly examined at least every six months, other lifting equipment every twelve, unless an examination scheme says otherwise. Local exhaust ventilation must be examined and tested at least once every 14 months, and the records kept for five years. Refrigeration and air conditioning holding 5 to 50 tonnes of CO2 equivalent must be leak checked at least every 12 months, 50 to 500 tonnes every six months and above that every three months, each doubled where leak detection is fitted. Air conditioning systems over 12kW must be inspected by an energy assessor at intervals of no more than five years. A pressure system may not be run without a written scheme of examination drawn up or certified by a competent person, and the scheme sets the interval.

For everything else the law asks for a suitable system of maintenance and leaves the frequency to the standards and your risk assessment. HSE is clear, for example, that there is no legal duty to test portable appliances every year, and that the law sets no fixed interval for reviewing a legionella risk assessment: review it regularly and whenever something changes.

What are the 31 checks, and how often are they done?

The table gives each check, the law or standard behind it and the interval a register should start from. Where the law fixes the interval, it says so. Where the interval comes from a British Standard or from practice, treat it as a starting point and follow your fire risk assessment, your insurer, the manufacturer and the competent person's report where they ask for more.

The 31 statutory checks for a commercial building

CheckThe law or standard behind itHow often
Fire risk assessmentFire Safety Order 2005 art. 9; recorded with its findings for every premises since 1 October 2023 (Building Safety Act 2022 s.156)Review regularly; yearly to start
Fire alarm servicingFire Safety Order art. 17 (a suitable system of maintenance); BS 5839-1Every 6 months
Weekly fire alarm testBS 5839-1Weekly, by the site
Emergency lighting, full duration testFire Safety Order art. 17; BS 5266-1Yearly
Emergency lighting, function testBS 5266-1Monthly, by the site
Fire extinguisher serviceFire Safety Order art. 17; BS 5306-3Yearly
Sprinkler or mist system serviceFire Safety Order art. 17; BS EN 12845Yearly
Dry riser inspection and testFire Safety Order art. 17; BS 9990Yearly
Wet riser inspection and serviceFire Safety Order art. 17; BS 9990Yearly
Fire damper testingFire Safety Order art. 17; BS 9999Yearly
Fire door inspectionsFire Safety Order art. 17Every 6 months
Kitchen extract cleaningFire Safety Order art. 17; BESA TR19 Grease (frequency by hours of use)Yearly to start
Electrical installation (EICR)Electricity at Work Regulations 1989 reg. 4Every 5 years
Portable appliances (PAT)Electricity at Work Regulations 1989 reg. 4; HSE says a yearly test is not a legal requirementBy risk; yearly to start
Lightning protectionBS EN 62305Yearly
Gas safety checkGas Safety (Installation and Use) Regulations 1998 reg. 35Yearly
Boiler and heating serviceGas Safety (Installation and Use) Regulations 1998 reg. 35Yearly
Pressure systems examinationPressure Systems Safety Regulations 2000 regs. 8 and 9As the written scheme says (set by law)
Local exhaust ventilation (LEV)COSHH Regulations 2002 reg. 9; records kept 5 yearsAt least every 14 months (set by law)
F-gas leak checkRegulation (EU) 517/2014 art. 4, as it applies in Great Britain12, 6 or 3 months by system size, doubled with leak detection (set by law)
Air conditioning inspection (TM44)Energy Performance of Buildings Regulations 2012 regs. 17 and 18, systems over 12kWAt most every 5 years (set by law)
Roof safety systems (fall arrest, eyebolts)Work at Height Regulations 2005 reg. 12; BS 7883Yearly
Automatic doors and roller shuttersPUWER 1998 reg. 5; BS EN 16005Every 6 months
Health and safety risk assessmentManagement of Health and Safety at Work Regulations 1999 reg. 3Review when no longer valid or after a significant change; yearly to start
Energy Performance CertificateEnergy Performance of Buildings Regulations 2012; MEES Regulations 2015 (E or better to let)Ten years to start
Legionella risk assessmentCOSHH 2002; HSE ACoP L8 (no fixed review interval in law)Review regularly and on change; two years to start
Water temperature monitoringHSE ACoP L8 and HSG274 Part 2Monthly
Asbestos management surveyControl of Asbestos Regulations 2012 reg. 4Once, then before works
Asbestos register and management plan reviewControl of Asbestos Regulations 2012 reg. 4 (at regular intervals)Yearly to start
Lift servicingPUWER 1998 reg. 5Every 6 months
Lift thorough examination (LOLER)LOLER 1998 reg. 9At least every 6 months for lifts carrying people, 12 months otherwise (set by law)

What records should you keep?

The certificate or report for each check, with its date, the next due date, who did it and the result; every remedial action it raised, with a due date and a note of how it was closed; the fire risk assessment, recorded with its findings; the asbestos assessment and management plan, with each review recorded; the LEV examination records for five years; the pressure systems written scheme and each examination; and the significant findings of your general risk assessment where you employ five or more people. An auditor or a client asks first for the gaps: checks with no record at all, not only checks that have lapsed.

How can AI help keep the checklist?

By doing the reading. A language model can read a certificate, a risk assessment or a service sheet and propose the date, the next due date, the result and each finding for a person to confirm. With every document already on file read that way, the checklist becomes a register in days rather than months of typing. The dates, the overdue list and the reminders should stay as written rules, and a person should confirm every reading before it is recorded.

What does this checklist leave out?

Duties that depend on the building or the work rather than the building type: higher-risk residential buildings under the Building Safety Act, construction work under CDM 2015, sector rules such as food hygiene or healthcare, and anything your lease, insurer or client contract adds. Scotland and Wales have their own fire safety law. Take advice on any particular building.

Where Servanda comes in

Servanda's facilities management software starts every Facilities site with these 31 checks as open questions, so nothing is assumed until a person confirms it applies. Each certificate is read by the model and confirmed by a person, findings get a due date from their priority, and every site shows what is in date, due soon, overdue or has no record at all. Book a demo to see it on your own buildings.

AI facilities management software · How to use AI in facilities management · AI property management software

The law

The legislation is the authority; this page is a plain summary for England, checked on 2026-11-23. Wales and Scotland have their own rules. Take advice on any particular building.