Commercial building compliance checklist.
In short
A commercial building compliance checklist lists the inspections, tests and assessments the law expects whoever controls a building to have done, how often, and the record that proves each one. Most come from the Fire Safety Order, the workplace and work equipment maintenance duties, LOLER, the pressure systems rules, COSHH, the gas, asbestos and electricity rules, the F-gas rules and the energy performance regulations. Only a few intervals are fixed by law; the rest come from British Standards and your own risk assessments. The 31 checks below are the ones a facilities register should start from, and a building keeps only those that apply.
What is a commercial building compliance checklist?
A commercial building compliance checklist is the list of statutory checks for an office, shop, industrial unit or mixed-use building: the fire risk assessment and the fire safety systems, electrical and gas safety, water hygiene, asbestos, lifts, pressure systems, ventilation, refrigeration, air conditioning and energy performance. For each check it says what the law or the standard asks, how often it is done, and what record proves it. It becomes a register once each line carries the date it was last done, the next due date and the certificate behind it.
Who is responsible for these checks?
It depends on the duty. Under the Fire Safety Order the responsible person, usually the employer or whoever controls the premises, must have a suitable and sufficient fire risk assessment and keep fire safety equipment under a suitable system of maintenance; where premises are part of a larger building, article 17 lets them make arrangements with the other occupiers, who must cooperate. The duty to manage asbestos falls on whoever has a contractual or tenancy obligation to maintain or repair the premises, or control of them where there is no such contract, shared in proportion. Employers must maintain the workplace, its equipment and work equipment in efficient working order. In a multi-let building the lease decides who does what, which is why a landlord, a managing agent and an FM provider often hold different parts of the same list.
Which intervals does the law set, and which come from standards?
The law fixes only a few. Lifts and lifting equipment that carry people must be thoroughly examined at least every six months, other lifting equipment every twelve, unless an examination scheme says otherwise. Local exhaust ventilation must be examined and tested at least once every 14 months, and the records kept for five years. Refrigeration and air conditioning holding 5 to 50 tonnes of CO2 equivalent must be leak checked at least every 12 months, 50 to 500 tonnes every six months and above that every three months, each doubled where leak detection is fitted. Air conditioning systems over 12kW must be inspected by an energy assessor at intervals of no more than five years. A pressure system may not be run without a written scheme of examination drawn up or certified by a competent person, and the scheme sets the interval.
For everything else the law asks for a suitable system of maintenance and leaves the frequency to the standards and your risk assessment. HSE is clear, for example, that there is no legal duty to test portable appliances every year, and that the law sets no fixed interval for reviewing a legionella risk assessment: review it regularly and whenever something changes.
What are the 31 checks, and how often are they done?
The table gives each check, the law or standard behind it and the interval a register should start from. Where the law fixes the interval, it says so. Where the interval comes from a British Standard or from practice, treat it as a starting point and follow your fire risk assessment, your insurer, the manufacturer and the competent person's report where they ask for more.
The 31 statutory checks for a commercial building
| Check | The law or standard behind it | How often |
|---|---|---|
| Fire risk assessment | Fire Safety Order 2005 art. 9; recorded with its findings for every premises since 1 October 2023 (Building Safety Act 2022 s.156) | Review regularly; yearly to start |
| Fire alarm servicing | Fire Safety Order art. 17 (a suitable system of maintenance); BS 5839-1 | Every 6 months |
| Weekly fire alarm test | BS 5839-1 | Weekly, by the site |
| Emergency lighting, full duration test | Fire Safety Order art. 17; BS 5266-1 | Yearly |
| Emergency lighting, function test | BS 5266-1 | Monthly, by the site |
| Fire extinguisher service | Fire Safety Order art. 17; BS 5306-3 | Yearly |
| Sprinkler or mist system service | Fire Safety Order art. 17; BS EN 12845 | Yearly |
| Dry riser inspection and test | Fire Safety Order art. 17; BS 9990 | Yearly |
| Wet riser inspection and service | Fire Safety Order art. 17; BS 9990 | Yearly |
| Fire damper testing | Fire Safety Order art. 17; BS 9999 | Yearly |
| Fire door inspections | Fire Safety Order art. 17 | Every 6 months |
| Kitchen extract cleaning | Fire Safety Order art. 17; BESA TR19 Grease (frequency by hours of use) | Yearly to start |
| Electrical installation (EICR) | Electricity at Work Regulations 1989 reg. 4 | Every 5 years |
| Portable appliances (PAT) | Electricity at Work Regulations 1989 reg. 4; HSE says a yearly test is not a legal requirement | By risk; yearly to start |
| Lightning protection | BS EN 62305 | Yearly |
| Gas safety check | Gas Safety (Installation and Use) Regulations 1998 reg. 35 | Yearly |
| Boiler and heating service | Gas Safety (Installation and Use) Regulations 1998 reg. 35 | Yearly |
| Pressure systems examination | Pressure Systems Safety Regulations 2000 regs. 8 and 9 | As the written scheme says (set by law) |
| Local exhaust ventilation (LEV) | COSHH Regulations 2002 reg. 9; records kept 5 years | At least every 14 months (set by law) |
| F-gas leak check | Regulation (EU) 517/2014 art. 4, as it applies in Great Britain | 12, 6 or 3 months by system size, doubled with leak detection (set by law) |
| Air conditioning inspection (TM44) | Energy Performance of Buildings Regulations 2012 regs. 17 and 18, systems over 12kW | At most every 5 years (set by law) |
| Roof safety systems (fall arrest, eyebolts) | Work at Height Regulations 2005 reg. 12; BS 7883 | Yearly |
| Automatic doors and roller shutters | PUWER 1998 reg. 5; BS EN 16005 | Every 6 months |
| Health and safety risk assessment | Management of Health and Safety at Work Regulations 1999 reg. 3 | Review when no longer valid or after a significant change; yearly to start |
| Energy Performance Certificate | Energy Performance of Buildings Regulations 2012; MEES Regulations 2015 (E or better to let) | Ten years to start |
| Legionella risk assessment | COSHH 2002; HSE ACoP L8 (no fixed review interval in law) | Review regularly and on change; two years to start |
| Water temperature monitoring | HSE ACoP L8 and HSG274 Part 2 | Monthly |
| Asbestos management survey | Control of Asbestos Regulations 2012 reg. 4 | Once, then before works |
| Asbestos register and management plan review | Control of Asbestos Regulations 2012 reg. 4 (at regular intervals) | Yearly to start |
| Lift servicing | PUWER 1998 reg. 5 | Every 6 months |
| Lift thorough examination (LOLER) | LOLER 1998 reg. 9 | At least every 6 months for lifts carrying people, 12 months otherwise (set by law) |
What records should you keep?
The certificate or report for each check, with its date, the next due date, who did it and the result; every remedial action it raised, with a due date and a note of how it was closed; the fire risk assessment, recorded with its findings; the asbestos assessment and management plan, with each review recorded; the LEV examination records for five years; the pressure systems written scheme and each examination; and the significant findings of your general risk assessment where you employ five or more people. An auditor or a client asks first for the gaps: checks with no record at all, not only checks that have lapsed.
How can AI help keep the checklist?
By doing the reading. A language model can read a certificate, a risk assessment or a service sheet and propose the date, the next due date, the result and each finding for a person to confirm. With every document already on file read that way, the checklist becomes a register in days rather than months of typing. The dates, the overdue list and the reminders should stay as written rules, and a person should confirm every reading before it is recorded.
What does this checklist leave out?
Duties that depend on the building or the work rather than the building type: higher-risk residential buildings under the Building Safety Act, construction work under CDM 2015, sector rules such as food hygiene or healthcare, and anything your lease, insurer or client contract adds. Scotland and Wales have their own fire safety law. Take advice on any particular building.
Where Servanda comes in
Servanda's facilities management software starts every Facilities site with these 31 checks as open questions, so nothing is assumed until a person confirms it applies. Each certificate is read by the model and confirmed by a person, findings get a due date from their priority, and every site shows what is in date, due soon, overdue or has no record at all. Book a demo to see it on your own buildings.
AI facilities management software · How to use AI in facilities management · AI property management softwareThe law
- Regulatory Reform (Fire Safety) Order 2005, article 9 (risk assessment)
- Regulatory Reform (Fire Safety) Order 2005, article 17 (maintenance)
- Building Safety Act 2022, section 156 (amendments to the Fire Safety Order)
- Workplace (Health, Safety and Welfare) Regulations 1992, regulation 5 (maintenance)
- Provision and Use of Work Equipment Regulations 1998, regulation 5 (maintenance)
- Management of Health and Safety at Work Regulations 1999, regulation 3 (risk assessment)
- Lifting Operations and Lifting Equipment Regulations 1998, regulation 9 (thorough examination)
- Pressure Systems Safety Regulations 2000, regulation 8 (written scheme of examination)
- Control of Substances Hazardous to Health Regulations 2002, regulation 9 (local exhaust ventilation)
- Regulation (EU) No 517/2014 on fluorinated greenhouse gases, article 4 (leak checks), as it applies in Great Britain
- Energy Performance of Buildings (England and Wales) Regulations 2012, regulation 17 (systems over 12kW)
- Energy Performance of Buildings (England and Wales) Regulations 2012, regulation 18 (air conditioning inspections)
- Electricity at Work Regulations 1989
- HSE: Maintaining portable electrical equipment, frequently asked questions
- Gas Safety (Installation and Use) Regulations 1998, regulation 35 (employers and the self-employed)
- Control of Asbestos Regulations 2012, regulation 4 (duty to manage asbestos in non-domestic premises)
- Work at Height Regulations 2005, regulation 12 (inspection of work equipment)
- HSE: Legionnaires' disease, Approved Code of Practice and guidance (L8)
- HSE: Legionella and landlords' responsibilities (no fixed review interval in law)
- GOV.UK: Non-domestic private rented property, minimum energy efficiency standard, landlord guidance
The legislation is the authority; this page is a plain summary for England, checked on 2026-11-23. Wales and Scotland have their own rules. Take advice on any particular building.